Aquaworx Remediator | Aquaworx Control Panel | Remediator FAQ | Control Panel FAQ | Photos
AquaWorx Remediator
What is a Transducer and how do I install it?
The Transducer replaces the floats. It senses liquid level by comparing
the air pressure in the bell to the air pressure in the tank. The panel
translates the difference in pressure to the liquid level relative to
the bottom of the Transducer bell. It attaches to a 1" PVC stand pipe
that mounts to the riser pump vault the same way a float tree would
mount.
How should I supply power to the panel?
The control power must be 120V. The pump circuit for the panel can be
wired either 120 volts or 240 volts depending on the pump requirements.
It is important to provide two designated circuits to the panel, one
circuit to the pump and one to the controls. The primary load draw is
the pump and the most likely component to trip the supply circuit
breaker. With two circuits, if the pump circuit tripped, power would be
available to the controls and would notify the homeowner of the problem.
What does Z-BIAS mean?
Each Transducer manufactured has a slightly different resistance
rating. Every Transducer is calibrated at the factory prior to
shipment. The calibration rating is recorded on the outside of the
transducer. This value needs to be programmed into the panel at start
up. This process matches the Aquaworx panel to the Transducer.
What is Auto-clear?
Timed system:
The air trapped in the Transducer bell needs to be replaced on
occasion. During periods of low or no flow the level will start to drop
in the tank. Once the level drops down to the start level the computer
tracks the next dose or doses as auto-clear doses. Since the start
level is typically set to one dose volume, the auto clear is typically
set to one (Example: a 40 gallon dose would translate to a 2" dose in
most 1,000 gallon tanks). During one of the doses the level will drop
below the start level. The next 2" dose will then end below the bottom
of the bell and the system will be idle until the liquid level rises
above the start level again. In the case of small doses multiple
auto-clear doses may be needed (Example: If the dose volume is 10
gallons, then 1/2" enough doses are required to draw the level to one
inch below the bell, so in this case an auto clear of 4 would be used).
Demand system:
In a demand system the start level becomes the pump ON and the bottom
of the bell becomes the OFF level. The auto clear is set in seconds -
typically 10 seconds. (Example: Pump will turn on at the start level,
pump down to the bottom of the bell then wait through the OFF time then
run the additional time to clear the bell).
Can I cut or splice the Transducer signal wire?
It is OK to cut the Transducer wire to length from the tank to the panel. However, the wire should NOT
be spliced. The high potential of corrosion when splicing the signal
wire will affect the signal and could reduce the accuracy of the unit.
The Transducers come in 6 different lengths eliminating the need for
field splicing. The lengths are: 40', 80', 120' 180', 240' & 300'.
What does VETO mean?
The VETO feature is a second timer setting (also known as an override
in some markets). If the flows increase above the Veto level, the VETO
timing replaces the normal time settings. If the level in the tank is
at or above the VETO level the panel will operate in the VETO schedule
below it operates in normal time settings.
I have input the new settings but it still runs the default program.
If the timer schedule and/or the level functions are changed, the AUTO feature must be selected. This will upload the new changes to the board and is found on the MARC unit between Manual A and Pump A settings.
Why does the alarm light always pulse?
When conditions are normal the alarm light flashes every 8 seconds.
This is called the "heart beat." This is a quick and easy indicator
that conditions are normal. If the alarm is solid red with a steady
tone the tank is in a high level condition. If the alarm is flashing
rapidly there is a different alarm condition. All alarms are
accompanied by an audible tone. However the tone may have been
silenced. If there is a question turn the power off and on again and
the alarm will sound again. If there is no tone check the connections
on the buzzer located on the bottom of the panel.
What is the volt draw of the transducer?
The Transducer has a 0.2 – 4.7 volt output with a pressure range up to 48" in the tank.
How do you define dose volume?
For the Aquaworx IPC panel the dose volume is defined as inches of
liquid in the tank. To convert from gallons to inches you must know the
gallons per inch of the tank. (Ex: a typical 1,000 gallon or 4' x 8'
square tank will have approx. 20 gallons of liquid per inch.) To
convert from gallons to inches simply divided the gallons of the dose
by the gallons per inch of the tank and this will give you inches for
the dose.
Why does my control panel read the EVENTs once a minute?
If the Log Status in the panel is set to Y (yes), then it will record
every event once per minute. This will cause the 4000 event to fill-up
quickly in the panel. The Log Status may be set to N (no). To change
this using the MARC, go to Mode settings and press enter. In the first
screen named Log Status, if you press enter the Log Status can be
changed to N (no).
Can the Transducer Bell get plugged and not function properly?
The Transducer bell shape was designed specifically for the waste water
environment and the Auto Clear function is designed to clear the
Transducer bell should it become clogged. It is important in a time
dose application to set the Auto Clear to at least one dose.
Why does my Transducer always read a 00.0" level?
In some cases the Transducer or circuit board may need to be replaced.
Check all connections. Test any component before installing it.
Checking a transducer with a bucket of water is an easy way to see if
the new transducer solved the problem.
Why does the Transducer read a constant level, (ex: 1.5- 6.5") even though the pump is running?
The Transducer wiring to the circuit board is not in the proper sequence. Make sure the input wires are RED (RD), BLUE (BL), and BLACK (BK) from left to right on the wire terminal strip attached to the circuit board.
How do you connect the Transducer to the control panel?
The input wires should be connected to the wire terminal strip attached
to the circuit board from left to right: RED (RD), BLUE (BL), and BLACK (BK)
How do you setup for a Redundant off Float?
The best way to use a redundant off is to wire a load rated float
switch in line with the power in the pump vault. Secondly, many pump
companies supply a "piggy back float" option.
Can I use a jumper to supply power to the alarm side of the panel?
No, it is important to provide two dedicated circuits to the panel
- one 120/240 volt circuit to the pump and one 120 volt to the alarm
controls. In a two circuit system, if the power supply for the pump
trips the breaker, then the alarm will still initiate during a high
level event.
How do I wire a panel for 240 Volt installations?
The control side of the panel must only be wired for 120 volt
installation. For the pump(s) power supply, the line side of the panel,
using 3 wire connect the Red wire to the Neutral or Pump L1 terminal
block and the Black wire to the Pump L2 terminal block. The White
neutral wire can be cut back.
What should I use to plug the transducer conduit to prevent sewer gases from entering the enclosure?
There is a variety of conduit sealing compounds available, but we
recommend, Chico SpeedSeal Compound, as it will quickly harden to a
dense, strong mass and are UL Listed and cUL Listed.
How do I setup a panel for demand dosing?
There three steps to remember when setting a IPC panel from Time dose to demand dose; 1) in the Mode settings the Stop at Zero
needs to be changed from N (no) to Y (yes). This will tell the panel to
stop pumping once the transducer reads a 00.0" liquid level, 2) in the
Pump A settings the Zero Bias should be set to 1
level above the calibrated level indicated on the Transducer bell (if
the ZB on the bell says 07 make it an 08, if 09 make it a 0A), 3) the Auto Clear setting needs to be changed from Dose to Seconds - typically 10-15 seconds.
Can you run the same Transducer wire in the conduit for the pump supply?
The Transducer wire can be run thru the same conduit as the pump power
supply without interference. However, the Transducer is a low voltage
wire and in some jurisdictions it is not allowed to run both High/Low
voltages in the same conduit. Check with both regional and State
Regulations first.
Can I use my IPC panel with multiple zones?
The IPC standard panel is not setup to handle addition I/O's. However,
if the Zones are set with a manual zone valve it is possible to run the
panel in multiple zones.
Can I setup the IPC panel with a Remote Alarm?
Yes, a remote alarm can be purchased as an option with all Aquaworx IPC
panels. The remote alarm will provide the same alarm sequence as the
alarms on the main enclosure. The remote alarm can be located up to
2000' away from the main control box. Contact customer service to
purchase.
How do I connect the IPC panel Remote Alarm?
Instructions come with the remote alarm.
How do I get the Events out of the IPC panel?
There are two options for retrieving the Event in the panel using the
MARC. 1st under the Events menu, you can retrieve each event the panel
has recorded by viewing the screen with a Date/Time & Liquid level
stamp. Each Event can be viewed one at a time.
2nd Using the MARC and a 1 GB SD card or less, insert the SD card into
the designated slot on the MARC. Scroll through the MARC menus to the
SD Card Settings menu, until the screen says Write Events. ENTER Y
(yes) to capture events to SD card, ENTER N (no) to skip. Note: The
MARC will show the events being transferred to the SD card. Once the
data transfer is complete, the SD card can be removed and placed in a
card reader connected to a PC. On the PC, click on the file to identify
the SD card events file. The file can be opened using a word pad or
spreadsheet. or text editing program.
What is the difference between DOSE, ADOSE & BDOSE in the Event log?
Dose = A recorded standard Dose from pump A.
ADose = A recorded Autoclear Dose.
BDose = A recorded Dose from pump B.
Can the panel be setup using two transducers?
Yes, using a IPC Sandfilter panel specifically for installations that
require two separate pump systems each needing a separate transducer
for each pump. (Product ID number: IPC-DSF)
In a small diameter pump chamber should I setup the panel for time dosing or demand dosing?
A small pump chamber can be setup for either time or demand pumping. It
is recommend that if the pump chamber has a long dosing range, (in
inches not volume) and the pump in the chamber is large enough to
quickly pump the chamber out, that it be setup using demand pumping.
The Stop at Zero setting should be set to Y (yes) so, the chamber will
not pump dry.
When I set the panel up to run both pumps what will happen?
This setting is designed to run both pump A and pump B during a Veto
level. This setting is used in conjunction with a Duplex panel to pump
the tank down faster. This should only be used if the pumps are small
and both pumps can run on one circuit or if it is a specialty panel
setup for individual circuits for each pump.
Can I put a heater unit inside the control panel?
Yes, Aquaworx offers a heater unit that can be easily setup in an
existing or new IPC panel. Contact customer service for more
information.
Why dose the panel have a transformer?
The transformer is used to provide a secondary voltage of 12V to the
circuit board. This 12V is used for supplying CB, alarm, relay control,
lamp, and input and transducer power. The transformer is Thermal
protected, meets Class II safety requirements and is UL/cUL listed.
What is the battery on the circuit board, and/or will I lose my events if the power goes out?
Its purpose is to keep the clock running, which will allow the data
logging to record when the power goes out and for how long the power
was off. The battery can last up to five years without a replacement
but, it is recommend that it be change every year. If the battery is
lost and the power goes out all data and all settings are retained and
will function once power is restored, however, the date and time will
re-set to 00.
Is the control panel UL/cUL Listed?
Yes, all Aquaworx IPC panel assemblies have agency UL/cUL listing.
What is the voltage of the Transducer and is it safe to put into the water?
The pressure sensor in the Transducer bell is encapsulated in epoxy
resin and is completely water proof. The operating voltage of the
sensor, depending on the liquid level, is between 0.2 to 4.7 volts.
What is a Varistor?
A verister is a variable resistor used to protect excessive current in
a circuit. Our varistor is connected between the incoming line and
neutral. This 130V varistor serves as over voltage/surge protection for
the controller.
Why use a solid state relay (SSR) and not a motor contactor?
The AC power switching is done via a solid-state relay. This type of
relay is very reliable. It has a quiet state change, (meaning no
clanking noise) relative to mechanical relays (which can be heard thru
walls when opened or closed). Optical isolation from the power and the
control is achieved with this relay, supplying the pump(s) with on/off
power. Our SSR is rated for 40 amps, max load for the panel is 20 amps
-safety factor of 2.
How do I setup the panel to handle a Sandfilter application?
Using the MARC controller, under the Mode settings, the Run Both / SFI
(Sand Filter Interface) menu will need to be set to Y (yes). This will
not allow Pump A to initiate if pump B has a high level alarm.
How do I set the time and date in the panel to start recording events?
This screen sets the current date and time in the panel. Using the MARC
under the Time Settings press the enter button. The following screens
will appear: Seconds (refers to the seconds in an hour), Minutes
(refers to the minutes of the hour), Hour (current hour in a 24 hour
format) and Day (refers to today's date), Month (refers to today's
month). Preset the screens to match the time/date.
How long does the clear air tube need to extend in the riser?
In most applications the air tube should extend out of the stand pipe
in the riser 10" forming a "Candy-cane shape". The tube may be cut to
length. It is important to always keep the open end of the tube pointed
down, so water or moisture doesn't accumulate in the tube.
The MARC unit is not recording events from my SD card?
If the MARC screen is going blank during the download, then it is
probably receiving too much current from the SD card. This may be
caused by too much data on the card, or too much memory on the card. We recommend a 1 Gigabit maximum SD card with dedicated use for the MARC.
How do I wire a Transducer to the panel for a Sandfilter application?
Follow the instructions provided with the panel. If the instructions
are lost you can download them from the AquaWorx website – www.aquaworx.com
Aquaworx Remediator | Aquaworx Control Panel | Remediator FAQ | Control Panel FAQ | Photos









